What size generator do I need to keep the essentials on?

To keep a refrigerator, a sump pump, a furnace blower, a router and some lights on, you need about 2,600 running watts and about 5,000 starting watts.

How the size is worked out

Champion Power Equipment and Generac print this method with their wattage charts, and Westinghouse’s manual adds the highest starting watts the same way. Total the running watts of everything that runs at the same time. Then add the single highest starting-watts figure on top, because motors rarely start at the same moment. The result is the minimum the generator has to supply.

Here is an essentials load built from those makers' charts:

Item Running W Start W
Refrigerator or freezer 700 2,200
Sump pump, 1/3 hp 800 1,300
Furnace blower, 1/2 hp 800 2,350
Wi-Fi router 24 none listed
Lights, four 75 watt bulbs 300 none listed
Total to start 2,624 4,974

The highest starting figure is the furnace blower’s, 2,350 watts, so the load needs 2,624 + 2,350 = 4,974 starting watts. Items with no starting figure listed add nothing.

What covers it

Product Verdict for this load
Generac Guardian 14 to 24 kW Covers it, all four
EcoFlow DELTA Pro 3 Starts it; lasts about 4.5 hours at this load
Jackery Explorer 5000 Plus Starts it; lasts about 5.5 hours at this load
Anker SOLIX F3800 Plus Starts it; lasts about 4.2 hours at this load
Tesla Powerwall 3 Starts it; lasts about 18.4 hours at this load
Enphase IQ Battery 10C Starts it; lasts about 13.7 hours at this load
Jackery Explorer 2000 v2 Cannot run it all at once: 2,200 W output
BLUETTI Elite 200 V2 Cannot run it all at once: 2,600 W output
Anker SOLIX C1000 Gen 2 Cannot run it all at once: 2,000 W output
EcoFlow DELTA 3 Plus Cannot run it all at once: 1,800 W output

The times are for a 24 hour outage and use the calculator’s starting guesses for hours of use, 4 a day for the sump pump and 8 for the furnace blower. Change them to your own.

For the standby generators, the figure used is the natural gas rating from Generac’s spec sheets, which is lower than the LP rating on the larger units: 14,000, 17,000, 19,500 and 21,000 watts for the 14, 18, 22 and 24 kW models. Generac says air-cooled standby generators have no separate surge rating, so the starting load has to fit within the continuous rating.

When the load grows

Add a well pump and a window air conditioner and the same method gives 4,824 running and 7,174 starting watts. Fewer products start that: the Jackery Explorer 5000 Plus and the Powerwall 3 among the stations and batteries, and every Guardian. The EcoFlow DELTA Pro 3 stops at 4,000 running watts, the Anker SOLIX F3800 Plus at 6,000 starting watts and the Enphase IQ Battery 10C at 7,080.

Central air conditioning, an electric range, a well pump on 240 volts and a heat pump are not in these tables, because their wattage is on the nameplate and varies widely. Generac’s advice is to list your essential loads, find which have a high starting wattage, and have a professional complete a load analysis for your home. For the whole house, that is the right next step.